◆ The built-in 24-inch LCD touchscreen enables high-resolution graphics of bird's-eye views and floor plans. The GUI (Graphic User Interface) is configured for easy operation of the GR-type receiver with color-coded statuses for greater visibility and intuitiveness for quick response in the event of an emergency.
◆ The status of analog detectors and fiber optic detectors can be viewed by event, printed out, and saved as an Excel file to maximize event and management efficiency.
-Formats: AC 220V, DC 24V, LCD type, accumulation/non-accumulation, analog type, (internal and external fire hydrant, sprinkler) equipment, (foam, water spray) fire extinguishing equipment, and smoke control equipment
-Number of Receiver system : Up to 16 systems for receivers, up to 256 systems when using repeat boards
-Accessible circuit per system : 250 (No distinction between 2 circuit repeaters, 4 circuit repeaters, and analog detectors)
-Communication method: repeater, analog sensor - 2 wire MULTI - DROP method
Receiver Network - TCP/IP, Infinite Connectivity
System track: Analog Loop line resistance up to 50Ω,
line capacitance value within 0.5uF, maximum length 1.2km
- Power used: AC 220V, 50/60Hz, DC24V 20A
- Reserve power: DC 12 V, 12Ah 2 ea, lead-acid battery
- Operating temperature: -10℃ to 50℃
- Usage humidity: RH 10% to 95% (No condensation)